Fire codes, the emergency plan and the state of the building make up this part of the NAB exams: which Life Safety Code edition CMS enforces, sprinklers and drills, the all-hazards preparedness rule, infection control and routine upkeep.

Topic 09 of 1018 questions, every option explainedPart of 3A · Care Setting (CORE 9 · NHA 7 scored items)From : domain 6 Care Setting, domain 4 Risk Management

18 questions on fire safety, emergencies and the plant

Tried so far: 0 of 18 · right: 0

Part of 3A · Life safety

During a summer heat wave, a facility certified after October 1990 must keep resident areas within which temperature range?

  1. 68-78 °F looks like a normal thermostat setting but drops below the 71 °F floor.

  2. Facilities first certified after October 1, 1990 must keep a temperature range of 71 to 81 °F (42 CFR 483.10(i)(6)).

  3. 85 °F exceeds the 81 °F ceiling and raises the risk of heat illness.

  4. 65 °F is far too cool for frail residents and below the required floor.

Reveal the key without picking
Part of 3A · Life safety

CMS currently surveys certified nursing homes against which edition of the Life Safety Code (NFPA 101)?

  1. The 2021 edition is not adopted either; the pending proposal is for 2024.

  2. CMS has enforced the 2012 editions of NFPA 101 and NFPA 99 since July 2016; a November 2026 proposal to move to the 2024 editions is not final.

  3. Newer editions exist, but CMS has not adopted the 2018 edition.

  4. The 2000 edition was the CMS standard until July 2016.

Reveal the key without picking
Part of 3A · Life safety

A nursing home first certified in 1985 has an existing, unaltered multi-resident bedroom with 256 sq ft of usable floor space. Under federal requirements, the most residents this room may hold is:

  1. Multi-resident rooms need at least 80 sq ft per resident (42 CFR 483.90(e)(1)); 256 ÷ 80 = 3.2, so three fit.

  2. Nothing limits a room this size to one resident.

  3. Four is the room ceiling for older facilities, but this room lacks space for a fourth resident.

  4. The two-per-room cap applies to facilities newly certified, built or reconstructed after November 28, 2016, not to this 1985 room.

Reveal the key without picking
Part of 3A · Life safety

Federal requirements for corridors in resident areas of a nursing home include:

  1. Carpet may be a design choice, but it is not a federal corridor requirement.

  2. Rest seating is good design, not a regulatory requirement.

  3. 42 CFR 483.90(i)(3) requires corridors in resident areas to have firmly secured handrails on each side.

  4. A rail along a single wall leaves residents unsupported whenever they walk the other way; the rule says both sides.

Reveal the key without picking
Part of 3A · Life safety

Under the Life Safety Code, a nursing home floor with 40 resident beds must be divided into at least how many smoke compartments?

  1. Four is not a minimum set by bed count; size and travel distance, not 40 beds, would call for more.

  2. The 2012 Life Safety Code requires a story used for sleeping by more than 30 residents to be divided by smoke barriers into at least two smoke compartments, so residents can move horizontally away from a fire.

  3. Larger floors can need more compartments because of size and travel-distance limits, but two is the minimum here.

  4. A single compartment would leave vertical evacuation down stairs as the only escape, which the code is built to avoid.

Reveal the key without picking
Part of 3A · Life safety

Surveyors find that the battery-powered exit and egress lights work when tested, but the facility has no written records of its monthly or annual tests. Which statement is correct?

  1. Both the monthly 30-second and yearly 90-minute tests must be documented.

  2. NFPA 101 (2012) requires battery emergency lights to be tested monthly for 30 seconds and yearly for 90 minutes, with written records kept for the authority having jurisdiction.

  3. Without records surveyors cannot verify past tests, so lights that work today do not prevent a citation.

  4. Documentation applies to battery emergency lighting too, not just generators.

Reveal the key without picking
Part of 3A · Life safety

A cognitively intact resident keeps stacks of newspapers and boxes piled around his bed, blocking access and adding a heavy fire load. He refuses to discard them. What is the BEST approach?

  1. His right to possessions stops where they endanger him or others, and a fire load and blocked access do.

  2. Discharge is a last resort, not the first answer to a safety problem that can be care-planned.

  3. Removing the items while he is away violates his rights and trust and invites the behavior to return.

  4. Residents may keep personal possessions unless they infringe on others' rights or health and safety (42 CFR 483.10(e)(2)), so the team agrees safe limits and storage with him and documents the plan.

Reveal the key without picking
Part of 3A · Life safety

A facility's evacuation plan relies on one local ambulance company to move all 120 residents. What is the MOST important gap to fix?

  1. Sending staff with residents matters, but it is secondary when there may be no vehicles at all.

  2. Reserved parking is a minor detail that changes nothing if the ambulances never come.

  3. Evacuation routes need no family consent; families are informed, not asked.

  4. In a regional disaster every hospital and nursing home calls the same vendors, so a one-company plan can fail completely; backup vendors, buses or mutual-aid agreements close the gap.

Reveal the key without picking
Part of 3A · Life safety

In the facility's on-site laundry, which routine task is MOST important for preventing dryer fires?

  1. Hot-water washing is an infection-control measure, unrelated to dryer fires.

  2. A five-year inspection interval is far too long to control lint buildup.

  3. Low heat lengthens drying time but lets lint build up just the same.

  4. Lint is highly combustible, and failure to clean it is the leading factor in clothes-dryer fires, so screens are cleaned after every load and exhaust ducts on a schedule.

Reveal the key without picking
Part of 3A · Life safety

A monthly generator test log shows: run time 30 minutes, transfer to emergency power in 8 seconds, load 15% of nameplate kW, exhaust temperature below the manufacturer's minimum. Which requirement was NOT met?

  1. Thirty minutes is the required monthly run time, so the run time was met.

  2. The 4-hour test is due once every 36 months, so it was not part of this monthly test.

  3. NFPA 110, applied through NFPA 99 (2012), requires the monthly 30-minute test at no less than 30% of nameplate rating or at the manufacturer's minimum exhaust temperature; 15% with low exhaust temperature meets neither.

  4. Transfer must happen within 10 seconds, and 8 seconds complies.

Reveal the key without picking
Part of 3A · Life safety

The receptionist answers a call from a person who says a bomb is hidden in the building. What should she do?

  1. Police are called first; any search follows the plan and their direction.

  2. Federal bomb-threat guidance (the CISA checklist) tells the call-taker to stay calm, keep the caller on the line and record exact words, voice and background sounds, then notify police and the person in charge.

  3. Announcing an evacuation herself oversteps: evacuation is decided by the person in charge with police under the emergency plan.

  4. Hanging up throws away the chance to learn where and when; a trace later gives far less than the caller might have said.

Reveal the key without picking
Part of 3A · Life safety

To save money, the CFO proposes replacing the facility's emergency exercises with one tabletop exercise every two years. How should the administrator respond?

  1. A facilitated tabletop can be the second exercise, but one every two years falls far short of two a year.

  2. No rule requires four full-scale exercises; overcorrecting the number is still the wrong rule.

  3. 42 CFR 483.73(d)(2) still requires LTC facilities to hold two exercises a year: an annual full-scale or facility-based functional exercise plus a second one that may be a tabletop.

  4. The 2019 burden-reduction rule eased testing for some outpatient providers but kept the twice-a-year schedule for LTC facilities.

Reveal the key without picking
Part of 3A · Life safety

Surveyors find an unlocked housekeeping closet with disinfectants on a unit where residents with dementia wander. Which response BEST corrects the deficiency?

  1. A sign is no barrier for a resident with dementia who cannot read or remember it.

  2. Disciplining one employee leaves every other storage area unchecked.

  3. An open nurses' station is still within residents' reach.

  4. Reachable chemicals on a dementia unit are an accident hazard (42 CFR 483.25(d)); securing the closet removes it, and an audit shows whether the problem is wider.

Reveal the key without picking
Part of 3A · Life safety

A facility's emergency plan describes the building and local hazards but says nothing about its residents who use ventilators, receive dialysis or have dementia. Which required element of the plan is missing?

  1. Sharing information with residents and families is a separate requirement, not the missing piece here.

  2. Fire drills come from the Life Safety Code, a separate requirement.

  3. 42 CFR 483.73(a)(3) requires the plan to address the resident population, including persons at risk, and the services the facility can provide in an emergency.

  4. This plan already covers building and local hazards; what it lacks is how those hazards affect these residents.

Reveal the key without picking
Part of 3A · Life safety

A renovation plan replaces the wardrobes in resident rooms with a shared clothing storage room on each hall. Does it meet 42 CFR 483.90(e)?

  1. 42 CFR 483.90(e)(2) requires individual closet space in the resident's bedroom, with racks and shelves the resident can reach.

  2. No separate dressing room is required; the rule is closet space in the bedroom.

  3. A locked room protects belongings but takes away the resident's own access to them.

  4. Staff delivery replaces the resident's own access with dependence on staff.

Reveal the key without picking
Part of 3A · Life safety

The administrator is updating the contact list in the emergency communication plan. Under 42 CFR 483.73(c), which contact must a nursing home include?

  1. News media are not required contacts; resident information goes out only under the plan's information-sharing rules.

  2. A trade association may help its members, but it is not on the required contact list.

  3. 42 CFR 483.73(c)(2) lists the Office of the State Long-Term Care Ombudsman among required contacts, with emergency officials and the state licensing and certification agency.

  4. The liability carrier is a business contact, not a required emergency contact.

Reveal the key without picking
Part of 3A · Life safety

A new addition will have five public entrances. Under the 2010 ADA Standards, at least how many must be accessible?

  1. 2010 ADA Standards 206.4.1 require at least 60% of public entrances to be accessible, and 60% of 5 is 3.

  2. Four (80%) is allowed but more than the minimum.

  3. One accessible entrance is the old "one door is enough" idea; the current standard is a percentage.

  4. Making all five accessible exceeds the requirement.

Reveal the key without picking
Part of 3A · Life safety

Housekeeping mops the main resident corridor at mid-morning, when residents walk to activities. Which practice BEST prevents falls?

  1. Confining residents so a chore can be finished restricts their movement for staff convenience.

  2. Mopping the full width leaves no dry path, and signs posted afterward come too late.

  3. Extra cleaner leaves a slippery residue that adds to the hazard.

  4. Keeping half the corridor dry and marked leaves residents a safe path, meeting the duty to keep the environment as free of accident hazards as possible (42 CFR 483.25(d)).

Reveal the key without picking

Your score and the next topic

–/18right so far on this page

This score is kept by your browser tab alone; closing the tab clears it, and the site records none of it.

Inside subdomain 3A Care Setting

The 2022 outline files buildings, safety and infection control under 3A Care Setting. All of it appears on both exams except 3A5, which is CORE only.

  • 3A1 Codes for the building, equipment, maintenance and grounds: the Life Safety Code and the Health Care Facilities Code as CMS adopts them.
  • 3A3 Safety and accessibility: ADA design standards, safety data sheets and hazardous materials.
  • 3A4 Facility management and environmental services: housekeeping, laundry and the condition of the plant.
  • 3A5 Information systems infrastructure: configuration, data security and technical controls. CORE only.
  • 3A6 Preventive and routine maintenance: equipment, mechanical systems, pest control.
  • 3A7 Infection control and sanitation: linens, kitchen, hand hygiene, healthcare-associated infections.
  • 3A8 Disaster and emergency planning, response and recovery, surveyed under Appendix Z.

The person-centered environment (3A2) is taught with quality of life. When the 2026 domains take effect on July 1, 2027, this material falls under Domain 6 Care Setting, and emergency preparedness shifts to Domain 4 Risk Management.

The Life Safety Code as CMS adopts it

CMS names the editions of NFPA 101, the Life Safety Code (NFPA) and of NFPA 99, the Health Care Facilities Code, that certified nursing homes must meet, along with the tentative interim amendments the regulation lists (42 CFR 483.90 (eCFR, 2026)). CMS adopted those editions in 2016 (Federal Register 2016-10043 (2016)).

A proposed rule published November 10, 2026 would move to the 2024 editions of both codes (Federal Register 2026-22812 (2026)). The proposal (docket CMS-3484-P) is not a final rule; until CMS publishes one, the editions named in 483.90 apply.

Within NFPA 101, nursing homes are health care occupancies. Chapter 18 covers new buildings and chapter 19 existing ones, and a building is judged by the chapter for its own case. Where the federal edition and a state or local code differ, the facility has to satisfy both.

Sprinklers, fire drills and the fire plan

  • Sprinklers: every long-term care facility must be protected throughout by an approved, supervised automatic sprinkler system installed to NFPA 13 (1999 edition) and maintained to NFPA 25 (1998 edition). The federal deadline for full sprinklering was August 13, 2013 (42 CFR 483.90(a)).
  • Drills: NFPA 101 has health care facilities run fire drills quarterly on each shift, at unexpected times and under varied conditions.
  • Written fire plan: the plan covers sounding the alarm, calling the fire department, confining the fire, moving residents out of danger, extinguishment and preparing for evacuation, and staff must know their part.
  • Defend in place: health care occupancies are designed so residents move horizontally to the far side of a smoke barrier first; taking residents down stairs or out of the building is the later step.

The NFPA codes are copyrighted. Read the free view on the NFPA 101 page (NFPA) or a licensed copy rather than secondhand summaries.

The CMS emergency preparedness rule

42 CFR 483.73 (eCFR, 2026) requires an emergency preparedness program with four core elements, plus power systems. Surveyors check it against the E-tags in State Operations Manual Appendix Z (CMS).

ElementWhat a long-term care facility must keep
Risk assessment and emergency plan
a documented facility-based and community-based assessment using an all-hazards approach that includes missing residents; the plan is revisited no less than annually
Policies and procedures
how residents and staff are fed, sheltered, tracked and, if necessary, evacuated, and how records are kept safe; reviewed at least annually
Communication plan
contact details and ways to reach staff, physicians, other facilities, families and emergency officials; reviewed at least annually
Training and testing
initial and annual training for all staff and contractors, plus exercises that test the plan and are documented
Emergency and standby power
generator placement, inspection, testing and maintenance that follow NFPA 99, NFPA 101 and NFPA 110

A 2019 burden-reduction rule let many other provider types review their plans every two years (Federal Register 2019-20736 (2019)); long-term care facilities still review theirs every year at minimum. The 2026 NAB domains list emergency preparedness under Risk Management rather than Care Setting, and its program overlaps with the risk work on QAPI and risk management.

Infection prevention and control in brief

42 CFR 483.80 (eCFR, 2026) requires an infection prevention and control program with:

  • surveillance and written standards;
  • a record of incidents and the corrective actions taken;
  • an antibiotic stewardship program with use protocols and monitoring;
  • at least one infection preventionist trained in nursing, medical technology, microbiology, epidemiology or a related field, who works at the facility at least part time and has completed specialized infection-control training.

CMS also expects a water management program that limits Legionella growth (CMS S&C 17-30 (2017, revised 2018)). Since April 1, 2024, its guidance calls for enhanced barrier precautions during high-contact care for residents with chronic wounds or indwelling devices, or with certain multidrug-resistant organisms (CMS QSO-24-08-NH (2024)). Day to day, infection control also means clean linen kept apart from soiled, safe food handling and hand hygiene everywhere.

The plant: maintenance, access and chemicals

A preventive maintenance program schedules inspection and service for every system and piece of equipment, documents the work, and includes pest control. New construction and alterations follow the 2010 ADA Standards for Accessible Design (ADA.gov). OSHA hazard communication requires an SDS on file and proper labeling for every hazardous chemical in the building. Federal rules for resident rooms, call systems, lighting and ventilation sit in the same section as the Life Safety Code, 42 CFR 483.90.

Building and emergency rules that get confused

Code confusions

  • NFPA 101 or NFPA 99. NFPA 101 is about getting people out and keeping fire and smoke away from them: egress, compartments, alarms, sprinklers. NFPA 99 covers the building’s health care systems, such as medical gas, electrical systems and emergency power.
  • Studying the 2024 codes. A move to them has only been proposed; check 483.90 for the editions CMS enforces.
  • The fire plan or the emergency plan. The fire plan comes from the Life Safety Code; the all-hazards emergency program under 483.73 is broader and also covers floods, outages, pandemics and missing residents.
  • Evacuating down the stairs first. Health care occupancies defend in place and move residents horizontally first.
  • Reading “infection preventionist” as a full-time post. The rule requires at least part-time work at the facility.
  • Applying another provider’s review cycle. Long-term care facilities still review the emergency plan at least annually.

Code editions and the emergency rule

Do state fire codes still apply on top of the CMS Life Safety Code?

Yes. 42 CFR 483.90 sets the code editions for federal certification, and states and localities can enforce their own fire and building codes as well. A facility has to satisfy both.

What are the core elements of the CMS emergency preparedness rule?

Four: the all-hazards risk assessment the plan rests on, written emergency procedures, a communications plan, and staff training plus exercises. Long-term care facilities also have requirements for emergency and standby power.

Where is emergency preparedness in the NAB outline?

On exams before July 1, 2027, it is item 3A8 under 3A Care Setting, which accounts for 9 of 100 scored CORE questions and 7 of 60 scored NHA questions. From that date, the 2026 domains list it under Domain 4 Risk Management on both CORE and the NHA line of service.